Inspection History: ELECTRIC - FINAL

Permit Number - T00CM05792

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/27/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
11/26/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*POLES 1.) SPLIT BOLT LISTED FOR RUN & TAP ONLY. 2.) BONDING JUMPER UNDER SIZED 3.) SEPARATE GROUNDING ELECTRODE & GROUNDING EQUIPMENT CONDUCTOR ROOF. 4.) PROTECT SEAL TITE WHERE PASSING THROUGH UNIT 5.) USE APPROVED FITTING FOR SEALTITE.