Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/20/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/07/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PARTIAL 1.) COMPLETE ELECT. HI VOLTAGE AT CONDENSING UNITS W/PROPER FUSING. 2.) PROVIDE MANUFACTURES INST. INSTRUCTIONS SHOWING CLEARANCE, CLEARANCE FOR SERVICE, ETC. FOOT PRINT. FOUR CONDENSERS APPEAR TO BE TO CROWDED FOR PROPER OPERATION 3.) CONDENSATE TERMINATIONS IMPROPER CANT DUMP INTO ALLEY OR PUBLIC WAY SOLID PARKING OR SIDE WALL. WANT TO REVIEW THIS WITH SOME ONE ON JOB SITE. |