Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM05767
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
04/02/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PLEASE SUPPORT POWER POLE WHIPS UP OFF OF THE GRID. 2.) DATA CALBES NEED TO BE SUPPORTED UP OFF OF THE GRID. 3.) BRING ALL DATA CABLES DOWN POLE CHASE. 4.) PLEASE PROVIDE PAPER WORK FOR POWER POLES AS REQUESTED. | |
03/20/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*WORK DONE BY ELECTRICAL CONTRACTOR FINISHED. INSPECTIONS WILL BE REQUIRED FOR CASH WRAPS INSTALLATION.POWER MAY BE ENERGIZED OPEN COMPLETION OF ALL OTHER TRADE INSPECTIONS PLEASE HAVE LAST INSPECTION NOTIFY ME FOR RELEASE. | |
03/18/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1. PLEAE LABEL PANELS ON OUTSIDE COVERS & LIGHTING CONNECTOR 2. NEUTRAL LUG W CT CAN NEEDS TO BE TIGHTEN. * WALL PACKS ACCORDING TO SPEC BOOK MEET LIGHTING CODES. | |
03/15/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) BOND DEVICE IS NEEDED AT BOTH SIDES OF NIPPLE 250-94 2.) BONDING JUMPERS TO BE SIZED PER CODE 250-102. 3.) PLEASE VERIFY WALL PACKS MEETS TUCSON LIGHTING CODES. 4.) PLEASE SUPPORT CONDUIT AS PER CODE. | |
03/14/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
03/13/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |