Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T00CM05767
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2002 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000* | |
02/22/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*UNDERGRD. APPROVED POLE BASES | |
02/15/2002 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999*1.) UNDER GROUND TO BE BURRIED TO CORRECT DEPTH PER CODE 300-5. IF CONCRETE IS TO ENCASE CONDUIT WE NEED TO SEE ENCASEMENT. 2.) POLE BASE NOT ON PLANS. PLEASE PROVIDE REVISED DRAWING FOR POLE AND BASE. PLANS TO BE APPROVED SHOWING TYPE LIGHT & POLE, LOAD CACULATIONS, AND ASE STRUCTIAL. | |
02/13/2002 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0240*1.) 3/4" PVC TO BE BURIED TO CORRECT DEPTH IN PARKING LOT PER CODE 300--24" | |
01/23/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* |