Permit: T00CM05767

Parcel: 115050420


Addresses:

131 W GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T00CM05767

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2002 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*
02/22/2002 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*UNDERGRD. APPROVED POLE BASES
02/15/2002 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*1.) UNDER GROUND TO BE BURRIED TO CORRECT DEPTH PER CODE 300-5. IF CONCRETE IS TO ENCASE CONDUIT WE NEED TO SEE ENCASEMENT. 2.) POLE BASE NOT ON PLANS. PLEASE PROVIDE REVISED DRAWING FOR POLE AND BASE. PLANS TO BE APPROVED SHOWING TYPE LIGHT & POLE, LOAD CACULATIONS, AND ASE STRUCTIAL.
02/13/2002 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0240*1.) 3/4" PVC TO BE BURIED TO CORRECT DEPTH IN PARKING LOT PER CODE 300--24"
01/23/2002 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*