Permit: T00CM05756

Parcel: 11504568A


Addresses:

830 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM05756

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/29/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
10/26/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*RECALL WHEN NOTES 12 & 13 CAN BE VERIFIED. MAIN SERVICE DISCONNECTS OK NOTES 12 & 13 (BELOW) NOT AVAILABLE.
09/23/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) NEED BONDING DEVICE BEFORE 1ST DISCONNECTING MEANS IN GUTTER. 2.) LOOSE CONDUIT AND SEALTITE FITTINGS 1ST LEVEL AT TOWER.
07/19/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) NEED BOND BUSHING ON CONDUIT TO THE FIRST DISCONNECTION MEANS 2.) TIGHTEN FIGHTTING AT GUTTER 3.) NEED BONDING JUMPER TO BOND BUSHING AT MAIN DISCONNECTS 4.) NEED REJECTION CLIPS. 5.) IDENTIFY GROUND CONDUCTOR 6.) FINISH INSTALLING BOND BUSHING PANEL AC-2 7.) SUPPORT CONDUIT AS PER CODE 8.) LOOSE FITTING ON LB 9.) WORKING CLEARANCE IN FRONT OF A/C DISCONNECT 10.) INSTALL BOND SCREW 11.) LOOSE SEAL TITE FITTING 12.) NEED TO SEE REVISED ELECTRICAL PLANS. 13.) NOTE: NEED TO RENEW PERMIT FOR PARKING LOT LIGHTING AND HAVE INSPECTIED FOR FINAL CLEARENCE.