Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM05756
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
10/26/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*RECALL WHEN NOTES 12 & 13 CAN BE VERIFIED. MAIN SERVICE DISCONNECTS OK NOTES 12 & 13 (BELOW) NOT AVAILABLE. | |
09/23/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) NEED BONDING DEVICE BEFORE 1ST DISCONNECTING MEANS IN GUTTER. 2.) LOOSE CONDUIT AND SEALTITE FITTINGS 1ST LEVEL AT TOWER. | |
07/19/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) NEED BOND BUSHING ON CONDUIT TO THE FIRST DISCONNECTION MEANS 2.) TIGHTEN FIGHTTING AT GUTTER 3.) NEED BONDING JUMPER TO BOND BUSHING AT MAIN DISCONNECTS 4.) NEED REJECTION CLIPS. 5.) IDENTIFY GROUND CONDUCTOR 6.) FINISH INSTALLING BOND BUSHING PANEL AC-2 7.) SUPPORT CONDUIT AS PER CODE 8.) LOOSE FITTING ON LB 9.) WORKING CLEARANCE IN FRONT OF A/C DISCONNECT 10.) INSTALL BOND SCREW 11.) LOOSE SEAL TITE FITTING 12.) NEED TO SEE REVISED ELECTRICAL PLANS. 13.) NOTE: NEED TO RENEW PERMIT FOR PARKING LOT LIGHTING AND HAVE INSPECTIED FOR FINAL CLEARENCE. |