Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T00CM05756
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1. BASE OF TOWER ENTRY OK TO COVER 2. 2010 AT SERVICE -2-2" LINES FROM GUTTER TO 2 NEW DISCONNECTS, OK TO COVER. | |
04/09/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0240* 1) NEED BLDG DEVICE BOTH END OF CONDUIT BEFORE 1ST DISCONNECTING MEANS TIGHTEN BOND BUSHINGS 250-94 2) LOOSE FITTINGS 3) SUPPORT CONDUIT AS PER CODE |
|
03/26/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK NORTH WING CEILING | |
02/21/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* NOTES: OK HARD CEILING SOUTHEAST CORNER OF MAIN SANTUARY | |
02/06/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK SOUTH WING |
|
02/05/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | 1) JUNCTION BOXES TO BE ACCESSABLE |