Permit: T00CM05755

Parcel: 117023270


Addresses:

1005 N 9TH AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/05/2001 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
03/29/2001 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0340*/LOST 1/2 PSI IN 10 MINUTE PERIOD. NEXT GAS TEST MUST BE WITH A MINIMUM OF 10 PSI ON GAUGE.