Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/13/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/12/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/NEUTRAL WIRES NOT PERMITTED TO TERMINATE MORE THAN SINGLE WIRE UNDER EACH TERMINAL (ONLY EXCEPTION IS GROUND WIRES OR LISTED MULTIWIRE TERMINALS), RETURN AIR VELICT VENTS REQ GRILLE'S, T-STAT NOT CONNECTED |