Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*OK FOR C OF O IN OFFICES ONLY NO C OF O. FOR WAREHOUSE. | |
| 08/02/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*PROVIDE A SECONDARY DRAIN ON AIR HANDLERS AS PER PLAN. HOOK UP OVERFLOW SENSORS ON CONDENSATE PUMPS. PROVIDE CLEAR ACCESS FOR REMOVAL OF FITTERS. INSULATE 90 ELBOW ON 2ND FLOOR. PROVIDE A PERMANENT LADDER ON ROOF AT PARAPET. SEE SEC. 321.8 NOTE #3 1994 UMC. CORRECT & RECALL FOR FINAL. | |
| 06/13/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*1)MOVE ALL THREAD AND UNISTRUT BLOCKING ACCESS TO FAN COIL.INSTALL CONDENSATE DRAIN LINES.2)INSTALL A TRAP ON CONDENSATE DRAIN ON PACKAGE UNIT.INSTALL OUTSIDE AIR VENT.3)GAS SHUT OFF MUST BE WITHIN 3' OF THE UNIT ON ROOF.4)FINISH INSTALLING MINI SPLIT UNITS.O.K. FOR TEMP C OF O. |