Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/29/2000 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 12/28/2000 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/1. WATER TEST NEEDS TO BE MINIMUM HEIGHT 42". 2. SEE UPC STANDARD INSTALLATION REQUIREMENTS SEC 316.1.5. THREADED FITTING NEED TO BE ACCESSIBLE. 3. CHICAGO LOOP PROVIDE SAN T'S AND CLEANOUT AT FOOT VENT OR PROVIDE TEST AT INTERMEDIATE INSPECTION. 4. A REINSPECTION FEE WILL BE IMPOSED IF INSPECTION IS CALLED IN AGAIN WITH NO CHANGE TO 00010 INSPECTION |
| 12/22/2000 |
PLUMBING - ROUGH, SOIL |
|
Denied |
1. PROVIDE APPROVED COMBO Y AT SEWER CONNECTION NO THREADED FITTINGS UNDERGROUND. 2. PROVIDE SAN T AT CHICAGO LOOP FOR DRAIN LINE AND CLEANOUT AT FOOT VENT. 3. PROVIDE APPROVED PLANS FOR INSPECTION. |