Permit: T00CM05700

Parcel: 10511061R

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM05700

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
03/28/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) GFI BEHIND STONE FOUNTAIN NEED TO BE ACCESSABLE 2) STRAP M/C CABLE AS PER CODE UNDER CASH WRAP
3) MISSING FACE PLATES UNDER CASH WALL
4) PROTECT RECEPTICLES FROM COMBUSTABLE MATERIAL 5) INSTALL M/C CABLE IN FITTINGS
6) SECURE FIXTURES 7) SUPPORT CONDUIT AS PER CODE ABOVE BATH 8) NEED BONDING DEVICE AT PANELS 9) FUSES TO BE RK-1 10) FINISH PREVIOUS LIST
03/26/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* OK PENDENT LIGHTING ABOVE CEILING AND MAKE UP OK RECESSED CANS SALES AREA, FITTING ROOMS 1) NEED PLATFORM TO ACCESS JUNCTION BOXES ABOVE HARD CEILINGCOVE LIGHTING; 2) STRAP M/C CABLE AS PER CODE 3) SECURE BALLAST
03/15/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) WORKING CLEARANCE IN FRONT OF PANEL "A" 2) NEED BOND DEVICE MAIN DISCONNECT 3) USE CORRECT FITTINGS 4) LOOSE FITTINGS 5) SECURE MAIN DISCONNECT 6) BOND GROUNDED CONDUCTOR TO GROUNDING ELECTRODE SYSTEM 7) VERIFY GROUNDING ELECTRODE SYSTEM TO STRUCTURAL STEEL
03/02/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*