Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM05700
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/28/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) GFI BEHIND STONE FOUNTAIN NEED TO BE ACCESSABLE 2) STRAP M/C CABLE AS PER CODE UNDER CASH WRAP 3) MISSING FACE PLATES UNDER CASH WALL 4) PROTECT RECEPTICLES FROM COMBUSTABLE MATERIAL 5) INSTALL M/C CABLE IN FITTINGS 6) SECURE FIXTURES 7) SUPPORT CONDUIT AS PER CODE ABOVE BATH 8) NEED BONDING DEVICE AT PANELS 9) FUSES TO BE RK-1 10) FINISH PREVIOUS LIST |
|
03/26/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK PENDENT LIGHTING ABOVE CEILING AND MAKE UP OK RECESSED CANS SALES AREA, FITTING ROOMS 1) NEED PLATFORM TO ACCESS JUNCTION BOXES ABOVE HARD CEILINGCOVE LIGHTING; 2) STRAP M/C CABLE AS PER CODE 3) SECURE BALLAST | |
03/15/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1) WORKING CLEARANCE IN FRONT OF PANEL "A" 2) NEED BOND DEVICE MAIN DISCONNECT 3) USE CORRECT FITTINGS 4) LOOSE FITTINGS 5) SECURE MAIN DISCONNECT 6) BOND GROUNDED CONDUCTOR TO GROUNDING ELECTRODE SYSTEM 7) VERIFY GROUNDING ELECTRODE SYSTEM TO STRUCTURAL STEEL | |
03/02/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* |