Inspection Status: Denied
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/30/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SEAL TIE ON FIRE BLOCKING AT FIREPLACE |
| 01/25/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) FIREPLACE CHIMNEY STILL NOT COMPLETE 2) THIS IS THE FOURTH TIME THIS HAS BENN WRITTEN UP. NEXT FAILURE WILL INCUR REINSPECTION FEE |
| 01/24/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SECURE FIRPLACE FLUE GREAT ROOM 2) FLUE MUST BE 1" AWAY FROM COMBUSTIBLES FIREPLACE IN GREAT ROOM 3) SEE ITEM #1 FROM 1/22/02 INSPECTION, ENTIRE HOUSE ONLY NORTH SIDE OF HOUSE HAS A TEST 4) SEE ITEM #3 FROM 1/22/02 INSPECTION |
| 01/22/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) THE ENTIRE DWV SYSTEM MUST BE TESTED WITH WATER TO THE TOP (SEE ITEM 1 FORM 1/16 INSPECTION) 2) FIRE BLOCK STAIRWAY AT LANDING (SEE ITEM 7 ABOVE) 3) COMPLETE INSTALLATION OF FIREPLACE FLUE (SEE ITEM 6 ABOVE) |
| 01/16/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NO WATER TEST ON VENTS 2) FIRE BLOCK AT GAS LINE AT GARAGE 3) SECURE GAS LINE 4) BLOCK MECHANICAL 3 SIDES 5) INSTALL TOILET FLANGES 6) FINISH FIRE PLACE FLUE INSTALL 7) FIRE BLOCK AT STAIRS 8) MASTER BATH DROP CEILING |