Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 03/16/2001 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 03/15/2001 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/1. FOOTER MUST BE 12" BELOW NATURAL GRADE. 2. 4 EACH PA HD42 HOLDOWNS REQUIRED PER PLAN. |
| 01/09/2001 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/1. PARTIAL BOARD NOT ALLOWED EXPOSED TO ELEMENTS. 2. POST FOOTERS MUST BE A MINIMUM OF 12" X 12" PRESENTLY ON 8" CYLINDERS. 3. UNTREATED WOOD CANNOT BE IN CONTACT WITH SOIL OR CONCRETE AND MUST BE A MINIMUM OF 6" ABOVE SOIL. 4. DOUBLE 2 X 4 HEADER SPANNING 10'-0" OVER WINDOWS NOT ALLOWED. 5. SIMPSON A-23 CLIPS DO NOT PROVIDE 2000 LBS UPLIFT. 6. SIMPSON STRONG TIE FASTENERS CANNOT BE SECURED WITH DRY WALL SCREWS. 7. PORCH ADDITION BLOCKS NATURAL LIGHT FROM LIVING ROOM HAS ONLY ONE 3030 WINDOW WITH 5040 BLOCKED BY ADDITION. 8. ELECTRICAL FLEX CONNECTOR CANNOT BE ENCLOSED IN WALL EXPOSE ALL ELECTRIC. 9. SIMPSON PAHD 42 HOLD DOWNS NOT INSTALLED. THERE IS NO FOOTER UNDER WEST WALL. 10. ELECTRIC OUTLETS NOT INSTALLED IN FOYER. 11. SOUTH ENDS OF WEST WALL MUST HAVE 2'-8" BRACED PANEL. 12. EXPOSE ALL SIMSPN HARDWARE. 13. ELECTRIC WIRES CANNOT BE INSTALLED IN GARDEN HOSE CONDUIT. 14. OUTSIDE ELECTRIC OUTLET MUST BE GFCI PROTECTED. |