Permit: T00CM05667

Parcel: 117061660


Addresses:

311 E CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM05667

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/14/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/09/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) CAN NOT USE SHEET METAL SCREWS FOR GROUNDING. HOLD FINAL FOR WORK IN CAFE #1
05/04/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* ROOF: 1) CLEAN SURFACE BENEATH GROUND LUG 250-12 2) LABEL A/C DISCONNECT 3) PULL OUT DISCONNECT NOT LISTED AS JUNCTION BOXES PLEASE USE APPROVED BOXES
4) WEATHER PROOF COVER MISSING COVER-HOOD
5) ALL STRANDS OF WIRE TO BE UNDER LUG
6) WORK CLEARANCES INFRONT OF A/C #2
7) DOUBLE LUGGING A/C #1 8) SUPPORT CONDUIT UP OFF OF FRONT OF ROOF-LOWER ROOF
9) BOND JUNCTION ENCLOSURES 250-96
10) FITTING DISCONNECTED AND EXPOSED CONDUCTORS. OK KITCHEN *WORK TO BE DONE IN CAFE AREA #1 AT A LATER DATE HOLD FINAL FOR THIS WORK.
04/30/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* NEED ACCESS TO ALL AREAS PLEASE RECALL
04/25/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*NOT READY
04/04/2001 ELECTRIC - FINAL Not ready for Inspection 1) WORKING CLEARANCES IN FRONT OF SERVICE EQUIPMENT 2) NEED BONDING DEVICE BOTH SIDES OF NIPPLE 3) LABEL DISCONNECT AND PANEL
4) LABEL PANEL TO VOLTAGE 5) BOND GUTTER 250-96 6) SUPPORT CONDUIT AS PER CODE
7) NEED PERMANENT METAL ADDRESS LABEL
8) NEED REVISED PLANS APPROVED BY COT FOR SERVICE