Permit: T00CM05663

Parcel: 12912021B


Addresses:

1608 S FREMONT AV

Inspection Status: Partial Approval

Inspection History: FRAMING

Date Description Inspector Results Comments
06/11/2003 FRAMING Partial Approval FIRE STOP FURNACE ROOM AND CLOSET OK TO SHEET ROCK EXCEPT FOR CLOSET AND FURNACE ROOM
02/25/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) COMPLY WITH HEADER SCHEDULE-ALL FRAME MEMBERS SHALL BE ON EDGE 2) REMOVE ALL INSULATION FOR INSPECTION 3) REMOVE DRYWALL NAILS FROM H2.5'S AND USE TICO NAILS 4) HAVE LICSENSE ELECTRICIAN COMPLETE WORK 5) PROTECT ALL PIPES AND WIRES CLOSER THAN 1 1/4" FROM FACE OF STUDS 6) GET QUALIFIED PLUMBER TO CHECK ALL PLUMBING AND TEST ABS TOP OUT 7) FIRE BLOCK MISSING THRU-OUT 8) TRIMMER STUDS REQUIRED UNDER HEADERS
11/14/2001 FRAMING Not ready for Inspection 1) PLAN CALLS FOR 2 X 6 CEILING JOIST AT 24" YOU HAVE 2 X 4 AT 24" ON CENTER ( MAYBE OK IF YOU INSTALL 2 X 8 AT 16" ON CENTER FOR RAFTERS INSTEAD OF 24" ON CENTER YOU CAN KEEP THE 2 X 4 CEILING JOIST AND USE A STIFF LEG 2) MECHANICAL DUCTS METAL FITTINGS, NEED TO HAVE A RIB AROUND THE ENDS TO KEEP THE DUCT FROM SLIDING OFF
10/29/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) NO ACCESS TO SITE 2) TWO DOGS IN YARD