Permit: T00CM05642

Parcel: 112060720


Addresses:

2636 N GILL AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
01/24/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
01/18/2001 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/TUB AND SHOWER REQUIRE SAN "T" NOT COMBUS OK TO BOX OUT AND CHECK AT PRE SLAB OK TO CONTINUE.
01/11/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0305*/1. DRAIN AND SEWER LINE MUST BE CONTINOUSLY SUPPORTED ON AND UNDISTUBED OR COMPACTED NATURAL SOIL OR FILL. 2. FLAT AND REVERSE FLOW ON 2" DRAIN 1/4" PER FOOT SLOPE REQUIRED. 3. SANITARY T VENT FITTING NOT ALLOWED HORIZONTAL DRAIN OR SEWER AT CONNECTION TO EXISTING. 4. TUB AND SHOWER NOT PROPERLY VENTED. 5. WATER CLOSET NOT PROPERLY VENTED. YOU MUST BUILD TO PLAN.