Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/26/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/19/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. LAVATORY DIRTY ARMS NOT PROPERLY VENTED. WEIR HIGHER THAN VENT OPENING. 2. MANY ELECTRIC WIRES HAVE STAPLES DRIVEN TOO TIGHT. (LOOSEN) 3. ELECTRIC NMC CABLE NOT ALLOWED TO BE EDGE NAILED FLAT NAIL ONLY. 4. WIRE FROM SHOWER LIGHT SWITCH DAMAGED. REPLACE 5. UNDERSIZE MECH DUCT TO S.E. MBR. 6. GROUP ALL METAL ELECTRIC BOXES. 7. MAKE UP ALL GROUNDS IN ELECTRIC BOXES AND PROVIDE SWITCH GROUNDS. 8. TUB AND SHOWER UNITS NOT INSTALLED BACK GROUT FLOOR PENETRATIONS. 9. NAIL DOOR TRIMMERS TO STUDS AT 24" O.C. 10. EXCESS OF 24" O.C. AT STUDS 3 PLACES. 11. BUILD MECH TO PLAN OR REVISE PLAN TO AS BUILT. 12. PROVIDE NAME AND LICENSED NUMBER OF YOUR ELECTRIC AND PLUMBING CONTRACTORS. |