Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/01/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/24/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ALL BEDROOMS MUST HAVE BATTERY OPERATED SMOKE DETECTORS 36" FROM AIR REGISTERS, 18" FROM CORNERS AND 6- 12" OFF CEILING 2) KITCHEN COUNTER ELECTRIC OUTLETS MUST BE GFCI PROTECTED 3) LAUNDRY DRAIN STACK TO LARGE AND NOT PROPERLY VENTED MUST USE 2" RISER WITH DOWN STREAM VENT-AAV, OK 4) DRYER CABLE NOT PROPERLY SECURED OR PROTECTED 5) WATER HEATER AND FURNACE REQUIRE DOUBLE WALLED CLASS "B" VENT WITH 1" CLEARANCE TO COMBUSTIBLES 6) REAR PORCH POSTS REQUIRE 1" SEPERATION POST BASES-(PIB-44) 7) GARAGE EAST EVE WITHIN 36" OF PROPERTY LINE REQUIRE 1 HR FIRE RATING (5/8") 8) FRONT PORCH REQUIRES 4 X 6 BEAM 9) ABS PLASTIC VENTS ON ROOF REQUIRE LATEX PAINT PROTECTION AND PROTECT OR REMOVE OLD LAUNDRY DRAIN 10) EXTEND WATER HEATER T&P LINE TO 6-18" ABOVE GROUND 11) EXPOSE ADDITION FOOTING AT NORTH WEST CORNER TO A DEPTH OF 12" |