Permit: T00CM05636

Parcel: 10320075B

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T00CM05636

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/07/2001 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
08/17/2001 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*CONFIRMED CEILING PATCHED ROOM 201. CONFIRMED PROPER INSTALLATION OF FIRE/SMOKE DAMPERS IN COMPUTER ROOM. PROVIDE ANGEL IRON AROUND DAMERS IN ROOM 300,100. HAVE YOUR CONTRACTOR CHECK ALL FIRE DAMPERS FOR PROPER INSTALLATION. LEAVE CEILING OPEN NEAR DAMPERS FOR INSPECTION. CHECK DISCONNECT ON NEW UNITS FOR PROPER FUSING. REPAIR BROKEN CONDENSATE DRAIN LINES. INSTALL OUTSIDE AIR VENTS ON UNIT 25,29,28,27 ALL UNITS BLOCK & CLAMP ELEC. CONDUITS LABEL UNITS. STEP UP TO 1 WHEN 2 3/4" DRAINS TIE TOGETHER.
06/12/2001 MECHANICAL - INTERMEDIATE Partial Approval 1)ROOM 201 PATCH UPPER LID.2)FACULTY BREAK ROOM-PARALLELS ADJ.IMPROPER INSTALLATION OF FIRE DAMPERS, AS ORGINALLY INSTALLED, THREE SUPPLY/RETURN.3)ROOM 300.4)CONSULT ARCH./ENGINEER FOR DIRECTION! EXIST FIRE DAMPERS.