Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM05636
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
| 10/01/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) NEED LETTER TO VERIFY TERMINATION OF MAIN SERVICE ALSO IS GENERATOR DISCONNECTED OR WORKING CORRECTLY. | |
| 09/18/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) NEED REVISED PLANS APPROVED. BY CITY OF TUCSON. 2.) ELECTRICTION TO PROVIDE LETTER OF VERIFICATION OF CONNECTION AND TERMINATIONS AT MAIN SERVICE 3.) WORKING CLEARENCE VIOLATION AT MAIN SERVICE COULD NOT ACCESS ALL SERVICE SECTIONS. 4.) A REFEE MAY BE ASSESSED IF THESE CORRECTION ARE NOT TAKEN CARE OF BEFORE NEXT INSPECTION. ALL EXIT SIGN ARE WORKING. | |
| 09/06/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) NEED REUSED PLANS FOR JOB TO REFLECT WORK DONE OR INSTALL AS PLANS 2.) EXIT LIGHT BATTARIES NOT WORKING AS MARK UP ON D1.1. 3.) PLEASE HAVE ELECTRICIAN PRESENT NEXT INSPECTION TO OPEN EQUIPMENT AT SERVICE TO CHECK CONNECTION AND TERMINATIONS. *ROOF OK. | |
| 08/19/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 06/12/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1. SUPPORT CONDUIT AS PER CODE. 2. LOOSE FITTINGS. 3. SUPPORT CONDUIT ABOVE CEILING AS PER CODE. 300-11 4. USE LISTED & APPROVED JUNCTION BOXES 5. PLANS TO REFLECT WORK BEING DONE. CONTRACTOR IS USING EXISTING LOCATIONS & LIGHTS & SWITCHED, NEED ENGINEER APPROVAL ALSO FOR A/C UNITS. * OLD AREAS NOT UNDER CONSTRUCTION HAVE NOT BEEN CLEARED FOR OCCUPANCY. |