Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2001 | ELECTRIC - INTERMEDIATE | Approved | ||
| 08/19/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) DATA LAYING ON GRID 2.) SUPPORT CONDUIT AS PER CODE 3.) NEED CITY APPROVED REVISED PLANS TO REFLECT LOADS AND WORK AS BEING DONE . ROOF 1.) LOOSE SEALTITE FITTINGS 2.) LABEL A/C UNITS 3.) WORKING CLEARANCE IN FRONT OF A/C DISCONNECTS 4.) SUPPORT SEALTITE NEED OCCUPANCY INSPECTION FOR FINAL ALL AREAS OCCUPIED WITHOUT INSPECTION. | |
| 06/17/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK WALL COMPUTER ROOM ONLY.1)CONDUIT ABOVE CEILING NEED TO BE SUPPORTED AS PER CODE 300-11 AND 348. 2)FILL UNUSED OPENING IN JUNCTION BOXES. *NOTE OLD AREAS NOT UNDER CONSTRUCTION WILL NEED OCCUPANCY INSPECTION BE FOR FINAL IS RELEASED. |
|
| 06/12/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* |