Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T00CM05635
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/12/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
02/09/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0935* NO COMPLIANCE TO PREVIOS WRITE UPS. PLEASE PAY REFEE PRIOR TO FUTURE INSP. | |
02/08/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* CEILING TILES CLOSED NEED 8' LADDER ON SITE FOR ACCESS TO CEILING DISC SW. STILL NOT IN COMPLIANCE TO 110-26 N.E.C. TIE UP CABLE IN FRONT OF 12X12 J-BIX |
|
02/07/2001 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - Ri canceled | |
02/06/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* DISCONNECT SWITCH FOR FCU NOT IN COMPLIENCE WITH NEC 110-26 WORKING CLEARANCE, 36" IN FRONT, 30" HORIZONTAL SUPPORT 1 1/2" CONDUIT FOR SCAN POWER PER NEC WITHIN 3 AT TERMINATION AND AT 10' INTERVALS |