Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/23/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/22/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. OVER BORE AT DBL TOP PLATE. 2. PEX LINES NOT SECURE. 3. ELECTRICAL THRU OUT WITHIN 1 1/4 FROM EDGE OF STUDS. 4. REFRIGERANT LINES MISSING. |