Permit: T00CM05618

Parcel: 133554250

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/26/2001 FRAMING Approved IVRS - Inspection 0000*
01/25/2001 FRAMING Partial Approval IVRS - Inspection 0000*/1. 2/8A CALLS FOR GABLE END BRACING AT 8' O.C.-BRACES THAT ARE INSTALLED ARE LESS THAN 45 DEGREES. BRACES DO NOT ADEQUATELY WORK IF NOT BETWEEN 45 DEGREE AND 60 DEGREE.