Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/18/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/17/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/1. PROVIDE FHA 16 GA. STRAP AT DBL TOP PLATE GAS LINE. 2. SECURE GAS LINES SEE UPC TABLE 12-2. 3. SECURE PEX LINES 4' O.C. HORIZONTALLY. 4. PROVIDE ENGINEERS FIX AT SHEARWALL TRANSFERS SEE SUPERINTENDENT. BLOCKS BETWEEN TRANFERS BLOWN OUT REPLACE AS PER DETAIL 18/SD3. 5. PROVIDE 1/8 INCH CLEARANCE FROM COPPER TO METAL STRAPS. 6. AT ISOLATE PEX LINE FROM RCWB STRAP. 7. PROVIDE RE-ENFORCEMENT AT ENTRY WAY. |