Permit: T00CM05616

Parcel: 137337120

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/18/2001 FRAMING Approved IVRS - Inspection 0000*
01/17/2001 FRAMING Partial Approval IVRS - Inspection 0000*/1. PROVIDE FHA 16 GA. STRAP AT DBL TOP PLATE GAS LINE. 2. SECURE GAS LINES SEE UPC TABLE 12-2. 3. SECURE PEX LINES 4' O.C. HORIZONTALLY. 4. PROVIDE ENGINEERS FIX AT SHEARWALL TRANSFERS SEE SUPERINTENDENT. BLOCKS BETWEEN TRANFERS BLOWN OUT REPLACE AS PER DETAIL 18/SD3. 5. PROVIDE 1/8 INCH CLEARANCE FROM COPPER TO METAL STRAPS. 6. AT ISOLATE PEX LINE FROM RCWB STRAP. 7. PROVIDE RE-ENFORCEMENT AT ENTRY WAY.