Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00CM05615
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
12/11/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*BASEMENT "A" BLDG COMPLETED OK TO OCCUPY MECHANICAL. | |
11/28/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*SOUTHSIDE UNIT NEED CONDENSATE TRAP PAINT PVC. SEE DETAIL #16. M4.0 CALL DURING TIME INSTING FIRE DAMPER OK TO SUPPLY GAS. | |
11/16/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*GAS SHUT OFF VALVES MUST BE BEFORE THE UNION ON GAS LINE. 2.) PROVIDE FUSES IN ELEC. DISCONNECTS. PAINT EXPOSED PVC W/LATEX PAINT LABEL EQUIPMENT PERMANENTLY PROVIDE CONDENSATE TRAP ON AC 1 PROVIDE ADEQUATE BLOCKING UNDER AC1 PROVIDE FIRE/SMOKE DAMPERS AS PER PLAN. PROVIDE WIRING DIAGRAM FOR DAMPERS & REVISION FROM ENGINEER. PROVIDE TAPS ON CONDENSATE DRAINS RECALL FOR INSPECTION. |