Permit: T00CM05615

Parcel: 124081700


Addresses:

1333 E 10TH ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T00CM05615

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
12/11/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*BASEMENT "A" BLDG COMPLETED OK TO OCCUPY MECHANICAL.
11/28/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*SOUTHSIDE UNIT NEED CONDENSATE TRAP PAINT PVC. SEE DETAIL #16. M4.0 CALL DURING TIME INSTING FIRE DAMPER OK TO SUPPLY GAS.
11/16/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*GAS SHUT OFF VALVES MUST BE BEFORE THE UNION ON GAS LINE. 2.) PROVIDE FUSES IN ELEC. DISCONNECTS. PAINT EXPOSED PVC W/LATEX PAINT LABEL EQUIPMENT PERMANENTLY PROVIDE CONDENSATE TRAP ON AC 1 PROVIDE ADEQUATE BLOCKING UNDER AC1 PROVIDE FIRE/SMOKE DAMPERS AS PER PLAN. PROVIDE WIRING DIAGRAM FOR DAMPERS & REVISION FROM ENGINEER. PROVIDE TAPS ON CONDENSATE DRAINS RECALL FOR INSPECTION.