Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/03/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/11/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*BASEMENT "A" BLDG COMPLETED OK TO OCCUPY MECHANICAL. |
| 11/28/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*SOUTHSIDE UNIT NEED CONDENSATE TRAP PAINT PVC. SEE DETAIL #16. M4.0 CALL DURING TIME INSTING FIRE DAMPER OK TO SUPPLY GAS. |
| 11/16/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*GAS SHUT OFF VALVES MUST BE BEFORE THE UNION ON GAS LINE. 2.) PROVIDE FUSES IN ELEC. DISCONNECTS. PAINT EXPOSED PVC W/LATEX PAINT LABEL EQUIPMENT PERMANENTLY PROVIDE CONDENSATE TRAP ON AC 1 PROVIDE ADEQUATE BLOCKING UNDER AC1 PROVIDE FIRE/SMOKE DAMPERS AS PER PLAN. PROVIDE WIRING DIAGRAM FOR DAMPERS & REVISION FROM ENGINEER. PROVIDE TAPS ON CONDENSATE DRAINS RECALL FOR INSPECTION. |