Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/04/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*DISCUSSED WORKING CLEARENCE FOR A/C DISCONNECTS |
| 04/03/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 04/02/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES GAS LINES IN DEDICATED WORKING SPACE OF AC UNIT DISCONNECT SW'S ON ROOF.MUST HAVE 36" IN FRONT AND 30" HORIZONTAL PER ART 110-26 NEC. |
| 12/07/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*BASEMENT ONLY. |
| 11/29/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |