Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/03/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/30/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) PUBLIC WOMENS TOILET ROOM - MUST HAVE A MINUMUM OF 15" FROM CENTER LINE OF WATER CLOSET TO SIDE WALL OR OBSTRUCTION 2) NO BALANCE CHECK INSTALLED ON W/H RE-CIRC. LINE 3) EXPANSION TANK NEEDS TO BE SUPPORTED 4) WHERE THE RE-CIRC. LINE TIES INTO COLD WATER INLET AT WATER HEATER, WHAT PREVENTS THE HOT WATER FROM MIGRATING UPSTREAM? |
| 04/02/2001 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* NOT READY |
| 03/30/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) C.L. FOR DISCHARGE TUBE AT URINAL MUST BE MINIMUM 6" FROM C.L. TO TOP OF FIXTURE. SEE SEC. 603.3.1 94 UPC |
| 03/28/2001 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* 1) ABOVE CEILING OK, OK FOR GRID |