Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/25/2001 | ELECTRIC - FINAL | Cancelled | IVRS - Ri canceled | |
| 04/23/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTE: CONTRACTOR HAS NOT COMPLIED WITH INSPECTION WRITE-UP 4-20-01, A DOUBLE REFEE WILL BE ASSESSED NEXT INSPECTION IF NOT IN COMPLIANCE. OK LETTER FROM ARCH. CONCERNING ALUIM BUSS | |
| 04/20/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) FINAL APPROVAL OF ELECTRICAL SUBJECT LETTER FROM ARCH. IN REFERENCE TO NOTE #9 OF SHEET E-1. SPECIFIES BREAKER PANELS TO BE COPPER BUSS, CONTRACTOR INSTALLED ALUMINUM BUSSED PANELS. 2) MC CABLE FEEDING FIRE DAMPERS FOR POWER ARE NOT SUPPORTED ENTIRE LENGTH. CONTRACTOR LEFT OPEN J BOXES, UNTERMINATED WIRES. ALSO NOTE THAT ABOVE CEILING INSP. BY INSPECTOR WAS APPROVED BEFORE INSTALLATION OF ELECTRICALLY OPERATED FIRE DAMPERS BECAUSE THESE WERE NOT SHOWN ON ORIGINAL CITY APPROVED PLANS REFER TO PAST INSP. REPORTS BY INSPECTOR. 3) HAS NOT COMPLIED WITH ITEM #1 INSP WRITE UP 4-13-01 4) PANEL SCHEDULES STILL NOT INSTALLED PER SPEC'S SHEET E-1 ITEM #9 | |
| 04/18/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* WAITING ON REVISIONS FOR FIRE DAMPERS AND A/C UNIT REVISIONS | |
| 04/16/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* | |
| 04/13/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*NOTES: 1. BOND JUMPER FOR NEUTRAL BONDS AT SERVICE ARE COLOR CODED WHITE ON ONE END & GREEN ON THE OTHER END??? SHOULD BE GREEN BOTH ENDS, 2.BREAKER PANELS DO NOT MEET SPEC'S (COPPER BUSS) TYPED PANEL SCHEDULES. 3. LIFT TILES OR PROVIDE 8" LADDER TO VIEW ELECTRIC OPERATED FIRE DAMPERS, ALSO LOCATION. 4. APPROVED PLANS INDICATE NEW ELECTRIC SERVICE (E-2) THE EXISTING SERVICE IS OLD & OBSELETE.? | |
| 04/12/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) LABEL PANELS A AND B 2) REMOVE BOND JUMPER BETWEEN GROUND AND NEUTRAL BARS INTERIOR BREAKER PANELS (A&B) 3) SHEET METAL SCREW NOT ALLOWED FOR PANEL COVERS, USE LISTED SCREWS PROVIDED BY MANUFACTURER 4) NEUTRAL STILL NOT BONDED IN DISC. SW. PANEL CODED PROPER COLOR(WHITE) 6) AS BUILDS DO NOT REFLECT FIRE DAMPERS 7) NEW PANELS NOT PER SPECS SEE SPECS 8) NO REVISED PLANS 9) MODULAR FURNITURE NOT WIRED OR INSTALLED YET |
|
| 04/02/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935* | |
| 03/30/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) NEUTRALS NOT BONDED AT SERVICE 2) EQUIPMENT GROUNDS SHOULD BE CONNECTED AT GROUND LUGS NOT NEUTRAL BAR, AT SERVICE 3) LB OUTSIDE MISSING COVER 4) BLANK OFF HOLES IN GUTTER 5) 120V DAMPERS NOT WIRED YET. 6) MODULAR FURNITURE NOT CONNECTED YET 7) COUPLING APPEARS TO BE MISSING COMPRESSION RING OUTSIDE AT SERVICE 8) NEED REVISED PLAN TO REFLECT CHANGES APPROVED BY COT |