Permit: T00CM05599

Parcel: 133291750


Addresses:

8257 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
03/29/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
03/28/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245* 1) INSTALL KO SEALS IN BOXES MISSING KO'S 2) MC CABLE MUST HAVE APPROVED BUSHED CONNECTORS ON ENDS, CANNOT INSTALL IN EMT CONDUIT 3) COMPLETE WIRING FOR LIGHTING FIXTURES 4) MC CABLE FOR CONNECTION BY OTHER THAN THIS CONTRACTOR MUST BE TERMINATED AT END
03/26/2001 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*
02/12/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* CONDUIT AND JUNCTION BOXES
02/09/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* PA CONDUIT AND BOXES