Permit: T00CM05572

Parcel: 137070470

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T00CM05572

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2002 ELECTRIC - TEMP POWER FOR TEST Approved
12/07/2001 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection 0999*PLEASE HAVE LADDER AVAILABLE FOR ROOF UPON NEXT INSPECTION. 1.) SERVICE PANEL MUST BE LISTED SUITABLE FOR USE AS SERVICE EQUIPMENT. 2.) NEED GROUNDING BUSHINGS AND BONDINGS JUMPER THROUGH OUT RACEWAY TO SERVICE EQUIPMENT PANEL BOARD. 3.) EXTERIOR CONDUIT ENTRY REQUIRE SEALING FITTINGS TO MAKE RAINTIGHT. 4.) WILL NEED LETTER OF TORQUEING FOR THE SERVICE EQUIP. 5.) CONDUITS IN FRONT OF COMPRESSOR DISCONNECT IN WAY
11/30/2001 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection 0999*NOT READY NEED MORE OF THE ELECTRICAL COMPLETED LIGHTY ETC. PLEASE HAVE TEMP SHEET SIGNED OFF AND BAND POST.