Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 04/29/2002 |
ELECTRIC - TEMP POWER FOR TEST |
|
Approved |
|
| 12/07/2001 |
ELECTRIC - TEMP POWER FOR TEST |
|
Denied |
IVRS - Inspection 0999*PLEASE HAVE LADDER AVAILABLE FOR ROOF UPON NEXT INSPECTION. 1.) SERVICE PANEL MUST BE LISTED SUITABLE FOR USE AS SERVICE EQUIPMENT. 2.) NEED GROUNDING BUSHINGS AND BONDINGS JUMPER THROUGH OUT RACEWAY TO SERVICE EQUIPMENT PANEL BOARD. 3.) EXTERIOR CONDUIT ENTRY REQUIRE SEALING FITTINGS TO MAKE RAINTIGHT. 4.) WILL NEED LETTER OF TORQUEING FOR THE SERVICE EQUIP. 5.) CONDUITS IN FRONT OF COMPRESSOR DISCONNECT IN WAY |
| 11/30/2001 |
ELECTRIC - TEMP POWER FOR TEST |
|
Denied |
IVRS - Inspection 0999*NOT READY NEED MORE OF THE ELECTRICAL COMPLETED LIGHTY ETC. PLEASE HAVE TEMP SHEET SIGNED OFF AND BAND POST. |