Permit: T00CM05572

Parcel: 137070470

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T00CM05572

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2001 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection 0000*
10/15/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
10/12/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*PARTIAL.
10/11/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
10/10/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
10/08/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
10/05/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*TOW EXCEPT FOR FRONT OVER BEAMS.
10/04/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*TOP OF COLUMN & AT BEAM HEIGHT.
10/03/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*TOW REAR SCREEN OK TO GO 6' AT FRONT PIERS.
10/01/2001 REINFORCED MASONRY PRE-GROUT Partial Approval
09/28/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*REAR SCREEN REPAIR OK FRONT IL
09/27/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
09/25/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*4
09/24/2001 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*
09/20/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*4 VERTICAL REINFORCEMENT ABOVE STEM WALL AT WEST ENCLOSURE IS NOT LONG ENOUGH.1.) CLEAN MORTAR DEBRIS OUT OF GROUT CELLS 2.) MORTAR FINS MAY NOT EXCEED 1/2" IN GROUT CELLS 3.) WHERE IS YOUR VERTICAL REINFORCEMENT AT WEST ELEVATION EAST OF CHASE WALL.
09/19/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
09/18/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*KEEP VERTICAL REINFERCEMENT @ CENTER OF GREAT CELLS.
09/17/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
09/14/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*PARTIAL 2L WEST;1/2 NORTH.
09/12/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*LAP ON VERTICAL #S ASTM40 REBAR OK@ 25"
09/11/2001 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*1.) KEEP GROUT POUR 7" BELOW TOP OF BLOCK @ 1ST LIFT TO PROVIDE PROPER SPLICE DISTANCE.
08/09/2001 REINFORCED MASONRY PRE-GROUT Partial Approval