Permit: T00CM05565

Parcel: 128100780

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/23/2000 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
ABS UNDERGROUND OK TRANSITION FITTINGS OK WATER TEST OK
DWV PIPING OK COPPER PIPING OK
I STILL NEED TO SEE CONDENSATE PIPING OK TO COVER EVERYTHING ELSE
11/21/2000 PLUMBING - ROUGH, SOIL Denied BREAKROOM
COMBO ON FLOOR SINK LOWERS POINT OF VENT BELOW WEIR OF TRAP USE SANTEE
N/H BANDS ARE NOT APPROVED FOR CONNECTING ABS USE SHIELDED COUPLING (MISSIUN) AT FLOOR SINK AND WHERE TIED INTO MAIN
VTR OK