Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/08/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/03/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) SECONDARY DRAIN TO FC-1 PIPED INTO WRONG OUTLET ON UNIT. FC-1 IS CORRECT 2.)PROVIDE TRAPS ON SECONDARY DRAINS. 3.) AIR HANDLERS OVERFUSED. 30 AMP IS MAX. 4.) PROVIDE ACCESS TO ROOFTOP RECALL FOR FINAL. |