Permit: T00CM05551

Parcel: 122172750


Addresses:

3255 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/08/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
05/03/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) SECONDARY DRAIN TO FC-1 PIPED INTO WRONG OUTLET ON UNIT. FC-1 IS CORRECT 2.)PROVIDE TRAPS ON SECONDARY DRAINS. 3.) AIR HANDLERS OVERFUSED. 30 AMP IS MAX. 4.) PROVIDE ACCESS TO ROOFTOP RECALL FOR FINAL.