Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
05/09/2002 MECHANICAL - ABOVE CEILING Approved
04/30/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999* 1.) CANNOT OPEN COVERS ON ELEC. DISCONNECTS ON AIR HANDLERS RELOCATE AS NEEDED. 2.) MARK DATA PLATES ON AIR HANDLERS W/PROPER HEAT KIT INSTALLED & FUSE UNITS ACCORDINGLY. 3.)LABEL EQUIPMENT. 4.) DRAIN PANS DO NOT EXTEND BEYOND EACH END OF AIR HANDLERS. SEE SECTION 307.2.3. 2000 IMC. MUST DRAIN TO A CONSPICUOUS LOCATION.
04/12/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*1.) NO APPROVED MECH. PLANS ON SITE 2. PROVIDE SECONDARY DRAINS ON AIR HANDLERS AS PER SECTION 307.2.3 2000 IMC OR SECTION 310.1.1. 1994 UMC.
04/09/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) TYPE II HOODS WHERE ARE VENTS TERMINATING? 2.) CONDENSATE DRAINS, AIR HANDLERS. WHO IS RUNNING THEM? AND WHERE ARE THEY TERMINATING??
03/11/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*KEEP FRONT OF AIR HANDLERS ACCESS PANELS CLEAR FOR SERVICE.