Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/11/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 03/08/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245* 1.) SUPPORT MC WITHIN 12" OF TERMINATIN. SUPPORT TO FRAMING MEMBER OR STRUCTURE. SEE ART 334-12 N.E.C. 2.) SUPPORT EMT WITHIN 3' EACH TERM, 348-13. NEC. 3.) TIGHTEN SET SCREW CONNECTOR. |