Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00CM05551

Parcel: 122172750


Addresses:

3255 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/11/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/08/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245* 1.) SUPPORT MC WITHIN 12" OF TERMINATIN. SUPPORT TO FRAMING MEMBER OR STRUCTURE. SEE ART 334-12 N.E.C. 2.) SUPPORT EMT WITHIN 3' EACH TERM, 348-13. NEC. 3.) TIGHTEN SET SCREW CONNECTOR.