Permit: T00CM05546

Parcel: 137338170

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/17/2001 FRAMING Approved IVRS - Inspection 0000*
01/16/2001 FRAMING Partial Approval IVRS - Inspection 0000*/OK TO INSULATE. 1. BLOCK UNDER HIP AT BEARING WALL. 2. PROVIDE ENGINEERED AND C.O.T. APPROVED TRUSS CALC'S FRONT GABLE END TRUSS NEEDS WEBS 16" O.C. FOR VERTICAL RE-ENFORCEMENT AT OUT LOOKERS. 3. PROTECT ELECTRIC ROMEX THRU-OUT WITHIN 1 1/4 FROM EDGE OF ALL STUDS AND AT AC LINE WIRE. 4. REFRIGERANT LINE STRESSED BY FHA STRAP PROVIDE CLEARANCE, DISSIMILIAR METALS SHOULD NOT BE TOUCHING ISOLATE. 5. SECURE PVC CONDENSATE LINES 4' O.C. HORIZONTALLY.