Permit: T00CM05522

Parcel: 126210750


Addresses:

3231 E ARROYO CHICO

Inspection Status: Partial Approval

Inspection History: FRAMING

Date Description Inspector Results Comments
12/04/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) EXCLUDES NORTH BATHROOM
12/04/2001 FRAMING Approved IVRS - Inspection 0000*
10/29/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) GROUND ALL ELECTRICAL METER BOXES 2) PROTECT ELECTRICAL WIRES AT STUDS WITHIN 1 1/4 FROM EDGE 3) ELECTRICAL NOT COMPLETE 4) PROTECT ALL ABS AND COPPER TUBING 5) LOSSE ANCHOR BOLTS THRU-OUT AB'S MISSING 6) INSTALL TOILET FLANGE 7) BLOCK MECHANICAL 3 SIDES 8) NEED WATER TEST ON PLUMBING 9) PROVIDE CALC'S FOR BEAMS AT AZ ROOM AND ADDITION OK 10) REVISE FRAMING PLAN TO SHOW AS BUILT