Permit: T00CM05517

Parcel: 13417286A


Addresses:

638 S WESLEY AV


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T00CM05517

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/29/2001 FRAMING Approved IVRS - Inspection 0000$
01/23/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ALL EXCEPT SUPPORT 2 X 12 HEADER AND SHEAR WALL.
01/19/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*/1. STUD NOTCHED FOR OUTLET KITCHEN COUNTER LEFT SIDE OF WINDOW ADD BLOCK/SLAB, NOTCH TOO DEEP. 2. SUPPORT HOIZ. VENT KIT SINK NEGATIVE PITCH IN CEILING. 3. SAME PROBLEM WITH FRAMING AS UNIT TO NORTH 4. FLEX DUCT NOT CONNECTED TO TRUNK LINE HALL WAY. 5. NEED H20 PRESS TEST ALL PORTABLE H20 LINES. 6. SUPPORT GAS LINE AT ROOF PENETRATION. 7. NO PRESS ON GAS LINE. 8. STIFF LEG 2 X 2 AT HALL DROP. 9. NEED TUB BACKING.
01/12/2001 FRAMING Not ready for Inspection 1. MISSING DAMPER IN EXHAUST FAN IN REAR BATH. 2. SHED ROOF RAFTERS TO BE 16" O.C. PER PLAN. 3. ADD 2 X 4 CEILING JOIST AT TUB CENTER BATH. 4. BLOCK GAS LINE WHERE IT EXISTS THE WALL H20 HEATER. 5. HEADER 2 X 12, NEED A KING STUDS UNDER CENTER SUPPORT PLUS SHEAR WALL SW5 NOT INSTALLED UNDER SAME HEADER.