Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T00CM05517
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2001 | FRAMING | Approved | IVRS - Inspection 0000$ | |
| 01/23/2001 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ALL EXCEPT SUPPORT 2 X 12 HEADER AND SHEAR WALL. | |
| 01/19/2001 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/1. STUD NOTCHED FOR OUTLET KITCHEN COUNTER LEFT SIDE OF WINDOW ADD BLOCK/SLAB, NOTCH TOO DEEP. 2. SUPPORT HOIZ. VENT KIT SINK NEGATIVE PITCH IN CEILING. 3. SAME PROBLEM WITH FRAMING AS UNIT TO NORTH 4. FLEX DUCT NOT CONNECTED TO TRUNK LINE HALL WAY. 5. NEED H20 PRESS TEST ALL PORTABLE H20 LINES. 6. SUPPORT GAS LINE AT ROOF PENETRATION. 7. NO PRESS ON GAS LINE. 8. STIFF LEG 2 X 2 AT HALL DROP. 9. NEED TUB BACKING. | |
| 01/12/2001 | FRAMING | Not ready for Inspection | 1. MISSING DAMPER IN EXHAUST FAN IN REAR BATH. 2. SHED ROOF RAFTERS TO BE 16" O.C. PER PLAN. 3. ADD 2 X 4 CEILING JOIST AT TUB CENTER BATH. 4. BLOCK GAS LINE WHERE IT EXISTS THE WALL H20 HEATER. 5. HEADER 2 X 12, NEED A KING STUDS UNDER CENTER SUPPORT PLUS SHEAR WALL SW5 NOT INSTALLED UNDER SAME HEADER. |