Permit: T00CM05499

Parcel: 113093640

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/01/2002 FRAMING Approved IVRS - Inspection 0000*
05/23/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) 2 LAYERS OF 5/8" X DRYWALL REQUIRED ON INSIDE AND AN ADDITIONAL 5/8 MASONITE REQUIRED OUTSIDE SEE S2
01/25/2002 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) CARPORT FIRE WALL NOT COMPLETE
01/23/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) SEVERAL ROOF PANELS LOOSE-WEST SIDE. NOT NAILED OR SHINED 2) GROUND ALL METAL ELECTRIC BOXES 3) FIRE BLOCK ALL FURRED OUT AREAS 4) PLAN CALLS FOR 1 HR FIRE WALL AT CARPORT SEE 1/P-2 5) BOND GAS AND COPPER WATER LINES 6) REVISE PLAN AND HAVE APPROVED FOR ADDED ELECTRIC ATTIC EXHAUST FAN AND PROVIDE A MINIMUM 22 X 30 ACCESS TO UNIT AND ELECTRIC CONTROL 7) TRUSS DRAWINGS MUST HAVE CITY OF TUCSON APPROVAL STAMP 8) OUTSIDE GFCI OUTLETS REQUIRED FRONT AND REAR