Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/01/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 05/23/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) 2 LAYERS OF 5/8" X DRYWALL REQUIRED ON INSIDE AND AN ADDITIONAL 5/8 MASONITE REQUIRED OUTSIDE SEE S2 |
| 01/25/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CARPORT FIRE WALL NOT COMPLETE |
| 01/23/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SEVERAL ROOF PANELS LOOSE-WEST SIDE. NOT NAILED OR SHINED 2) GROUND ALL METAL ELECTRIC BOXES 3) FIRE BLOCK ALL FURRED OUT AREAS 4) PLAN CALLS FOR 1 HR FIRE WALL AT CARPORT SEE 1/P-2 5) BOND GAS AND COPPER WATER LINES 6) REVISE PLAN AND HAVE APPROVED FOR ADDED ELECTRIC ATTIC EXHAUST FAN AND PROVIDE A MINIMUM 22 X 30 ACCESS TO UNIT AND ELECTRIC CONTROL 7) TRUSS DRAWINGS MUST HAVE CITY OF TUCSON APPROVAL STAMP 8) OUTSIDE GFCI OUTLETS REQUIRED FRONT AND REAR |