Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) PLUMBING FINAL OK 2.) OK FOR C OF O. PENDING ANY OTHER INSPECTIONS. | |
| 06/14/2001 | PLUMBING - INTERMEDIATE | Partial Approval | 1)ALL CORRECTIONS MADE OK.2)OK TO COVER PLUMBING WALLS ONLY.3)OVERHEAD AND ROOF DRAIN NOT INSPECTED AT THIS TIME. | |
| 06/07/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1)VIE-I KNOW YOU ARE TRYING TO GET A PARTIAL INSPECTION, SO YOU CAN SHEET ROCK, HOWEVER, THERE IS STILL A REVENT BACK PITCHED.ALSO, CLEAN-OUTS ARE TO BE INSTALLED ON VERTICIAL PIPING.THE BACK PITCH HAS NOT BEEN CORRECTED ON THE ROOF DRAINS.(SEE NOTE #7 ABOVE).DO NOT COVER THE PLUMBING UNTILL DIRECTED TO DO SO.(IT HAS ALREADY STARTED).2)PLEASE HAVE THE PLUMBER MAKE ALL REQUIRED CORRECTIONS BEFORE CALLING IN FOR INSPECTION. | |
| 05/28/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1)NO APPROVED PLANS OR PERMIT ON JOB SITE.2)UNDERGROUND COVERED BEFORE INSPECTION.3)WILL NEED TO SEE 5# AIR TEST ON ENTIRE DWV SYSTEM AND DOCUMENTATION SUPPORTING THE CORRECT INSTALLATION OF ROUGH/SOIL PIPING, THIRD PARTY FIELD NOTES, COMPREHENSIVE PHOTOGRAPHS ETC.4)NO TEST ON COPPER WATER PIPING NOT COMPLETE.5)CONDENSATE PIPING NOT COMPLETE IN WALLS.6)BACK PITCH ON N/H REVENT.7)BACK PITCH ON ROOF DRAIN PIPING.8)NO TEST ON ROOF DRAINS. |