Permit: T00CM05488

Parcel: 137338960


Addresses:

6277 S BEARDSLEE DR

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
02/21/2001 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
02/15/2001 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*/SAME STATUS DOUBLE RE FEE REQUIRED.
02/14/2001 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*/1. "SUBSTANDARD INSTALLATION FOR HORIZONTAL FURNACE." SUPPORTS NOT NAILED OR SCREWED AS PER CROSS SECTION PROVIDED. 8D NAILS USED IN LIEU OF 16D SCREW AT BOTTOM STRAP, NOT AS PER SHEET. PROVIDE REFRIGERANT LINES IN DIRECT CONTCT WITH METAL STRAP AT OVERKNOTCHED DBL TOP PLATE. FURNACE FLUE VENT NOT INSTALLED PER UMC SEC. 805.1 THERMOSTAT WIRES UNDER CIELING NEED TO BE CONCEALED NAILS AT TOP CHORD ARE INSTALLED AT BOTTOM EDGE OF TOP CHORD WITHIN 1/8 OF BOTTOM EDGE SHEARWALL AT REFRIGERANT LINE EXIT BLOWN OUT OVER 4" NEEDS TO BE REINFORCED BY BLOCKS. PROVIDE 1' CLEARANCE AT FURNACE FLUE PIPES TO COMB. MATERIALS.
02/12/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/1. PROVIDE APPROVED DETAIL FOR MECHANICAL SUPPORT 2. PROVIDE CLEARANCES AS PER PLAN.
02/08/2001 MECHANICAL - INTERMEDIATE Denied