Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 03/12/2001 |
PLUMBING - SEWER HCS CONNECT |
|
Approved |
IVRS - Inspection 0000* |
| 03/08/2001 |
PLUMBING - SEWER HCS CONNECT |
|
Denied |
IVRS - Inspection 0999*/1. THE CONNECTION TO THE EXISTING SEWER IS NOT MADE. 2. YOU MUST HAVE A WATER TEST OF ALL UNDERSLAB PLUMBING TO INCLUDE THE NEW SHOWER AND WATER CLOSET. THE WATER TEST MUST BE MADE WITH A WATER COLUMN AT LEAST 42" ABOVE THE FINISHED FLOOR OF THE ADDITION. PRESENTLY YOU HAVE ONLY WATER IN THE DRAIN TRUNK LINE. 3. I AM UNABLE TO LOCATE YOUR EAST SIDE PROPERTY LINE PLEASE RE-ESTABLISH THE N.E. CORNER PIN. 4. YOU WILL NEED TO ESTABLISH A GROUND SYSTEM FOR THE NEW GARAGE. I RECOMMEND A UFER GROUND CONNECTIONS TO A 20 FOOT REBAR WITH #4 CU. CONDUCTOR. |
| 03/07/2001 |
PLUMBING - SEWER HCS CONNECT |
|
Denied |
IVRS - Inspection 0999* |