Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
Permit Number - T00CM05458
Inspection Description - PLUMBING - SEWER HCS CONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2001 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection 0000* | |
03/08/2001 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection 0999*/1. THE CONNECTION TO THE EXISTING SEWER IS NOT MADE. 2. YOU MUST HAVE A WATER TEST OF ALL UNDERSLAB PLUMBING TO INCLUDE THE NEW SHOWER AND WATER CLOSET. THE WATER TEST MUST BE MADE WITH A WATER COLUMN AT LEAST 42" ABOVE THE FINISHED FLOOR OF THE ADDITION. PRESENTLY YOU HAVE ONLY WATER IN THE DRAIN TRUNK LINE. 3. I AM UNABLE TO LOCATE YOUR EAST SIDE PROPERTY LINE PLEASE RE-ESTABLISH THE N.E. CORNER PIN. 4. YOU WILL NEED TO ESTABLISH A GROUND SYSTEM FOR THE NEW GARAGE. I RECOMMEND A UFER GROUND CONNECTIONS TO A 20 FOOT REBAR WITH #4 CU. CONDUCTOR. | |
03/07/2001 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection 0999* |