Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T00CM05456
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK 2.) OK FOR DRYWALL. | |
06/27/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) PLUMBERS TAPE NOT APPROVED STRAP 2.) SUPPORT T&P DRIAN ISOLATE METALS 3.) WATER TEST TO 42" 4.) INSTALL CONDENSATE PIPING. | |
06/22/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) PLUMBERS TAPE NOT APPROVED STRAP 2.) SUPPORT VERTICAL PIPING WHERE LOOSE IN THE WALL 3.) MINIMUM TWO PIPE DIAMETERS BETWEEN OF TRAP AND POINT OF VENT ON A TRAP ARM. |