Permit: T00CM05455

Parcel: 117142770


Addresses:

624 S RUBIO AV


Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T00CM05455

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
08/27/2001 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*WILL NEED WATER & GAS BOND ( AS APPLICABLE
08/23/2001 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*
08/21/2001 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*1.) NO RECORD OF UFER 2.) UFER TO TIE ALSO INTO NEUTRAL BAR AT SERVICE 3.) ONLY 1 #4 ALLOWED ON EQUIPMENT GROUND BAR TERMINAL NOT TWO. 4.) INSTALL BREAKERS AND TERMINATE CONDUCTORS FOR TEMP SERVICE. 5.) GAS & WATER BOND.