Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T00CM05449
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/29/2001 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
03/28/2001 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/1. CLEAR INSULATION FROM ALL BIRD BOARDS. 2. RE-SEAL PLENUM. 3. NO DISHWASHER DRAIN INSTALLED. 4. VENT FAN IN MASTER TOILET INOP. 5. CHANGE 60 AMP BREAKER TO 50 IN MAIN PANEL-#6 WIRE. | |
03/21/2001 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |