Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/02/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
1) BATH AND WASHER RECEPTICLES ON SAME CIRCUIT-SEPERATE WASHER NEEDS OWN CIRCUIT IN PANEL 2) BATHROOM GFI NOT IN-WIRES ENERGIZED-SHUT CIRCUIT AS BATH GFI SHOULD BE SEPERATE-PANEL SHOULD HAVE A SEPERATE WASHER AND BATH BREAKER 3) WHAT CAME ABOUT WITH THE JUMPER FROM THE GROUND BAR TO THE NEUTRAL BAR AT THE SERVICE AS WE HAD DISCUSSED? DID YOU FIND THE ORIGINAL JUMPER IN THE SERVICE? |