Permit: T00CM05427

Parcel: 134244370


Addresses:

6305 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/11/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O.
09/10/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*NEED TO SEE CONDENSATE DRAINS FOR WALK IN COOLERS RECALL FOR INSPECTION
09/07/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) PROVIDE SUPPORT UNDER COPPER REFER LINES AT CONDENSORS. INSULATE LINES AS NEEDED. 2.) PROVIDE 1" CLEARANCE AT WATER HEATER VENT THRU CEILING. 3.) PROVIDE OUTSIDE AIR HOODS FOR A/C UNITS 4.) FINISH WIRING SMOKE DETECTORS. 5.) PROVIDE CONDENSATE DRAINS FOR WALK IN COOLERS.