Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/12/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR FOR PERM. PWR. APPROVED. |
| 09/11/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0020*N.E.C. 110-22 REQUIRES EACH EQUIPMENT DISCONNECT BE MARKED WITH ITS POINT OF ORIGIN" THIS MEANS THE PANEL AND CIRCUITS FROM WHICH THE LINE FEEDERS ORIGINATE. THE UNIT EACH SWITCH FEEDS IS EVIDENT AND DOES NOT BE MARKED ON THE SWITCH. DO NOT USE MAGIC MARKER" ON EXTERIOR SURFACES USE PERMANENT LABELS ONLY. MAGIC MARKER IS OK INDOORS ONLY. PANELS S/B UNLOCKED TO INSPECT. THANKS MAC. |
| 09/10/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*ELECTRICAL CONTRACTOR 1.) INSTALL EXIT LIGHTS 2.) COMPLETELY COVER SWITCHES ON ROOF 3.) FINISH DINING RM LIGHTS OWNER HAVE YOUR INSTALL CONNECT YOUR EQUIPMENT SO AS WIRING METHODS CAN BE CHECKED. |
| 08/31/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |