Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T00CM05415
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
06/26/2001 | FRAMING | Partial Approval | 1) FRAME-OK, ALL BUT STAIRS NOT IN, OK TO DRYWALL | |
06/25/2001 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) FRAME OK-CANNOT APPROVE UNTIL ELECTRIC AND PLUMBING ARE COMPLETE 2) PORCH DECK AND STAIR NOT READY | |
04/18/2001 | FRAMING | Denied | IVRS - Inspection 0999*/1) PORCH 4X10 BEAM NOT BEARING POST ON SOUTH END 2) ROOF SHEATHING NOT PROPERLY FASTENED MANY AREAS NOT NAILED OR HAVE SHINERS 3) STAIRS NOT BUILT 4) EXTERIOR SHEATHING NOT ALL NAILED 5) 2/A2 NOT COMPLIED WITH BUILD TO PLAN OR REVISE PLAN TO AS BUILT 6) WINDOWS DELETED, REUSE PLAN 7) TOP PLATES MUST BEAR ON STUDS 8) HEADER REQ TO BE 3-2X8 9) POSTS AND BEAMS REQ'D TO BE DOUG, INSTALLED 10) PLUMBING NOT COMPLETED 11) ELEC GROUNDS REQUIRE A MECH FASTENER 12) HEADERS MUST BEAR ON TRIMMERS |